● Monitoring: AC Outgoing Branch Circuits Multi-metering (1-phase & 3-phase)
● Measurement: Voltage, Current, Frequency, Active Power, Reactive Power, Power Factor and etc
● Power Quality: 2nd~31st&Total Harmonic
● Communicaiton: RS485 (MODBUS-RTU)
● Rated Voltage: 220~264Vac L-N
● Rated Current: 50mA AC (via -/50mA CTs)
● Standard&Certificate: CE; IEC; LVD
Overview
With the rapid development of data center, the energy consumption problem of data center is becoming more and more prominent. The energy management and power supply and distribution design of data center have become a hot issue. Efficient and reliable power distribution system scheme of data center is an effective way to improve the power consumption efficiency of data center and reduce the energy consumption of equipment. In order to realize energy saving in data center, it is necessary to monitor each electrical load first. However, there are many load circuits in data center. Traditional measuring instruments cannot meet the requirements of cost, volume, installation, construction and other aspects. In this case, the multi-circuit monitoring device which is suitable for centralized monitoring in data center is necessary to be used. AMC16Z series AC precision power distribution monitoring device is specially designed for data center server power management.The device designed exquisite, can provide A + B 2 incoming and 96 outgoing’s electrical parameters, the input and output switch and the state of lightning protection device with real-time monitoring. All alarm threshold of measurement channels can be set in separate. Over-outgoing triggers system acoustooptic warning immediately. Highly integrated monitoring loop is realized in the volume of traditional instruments.Product Features
Dual AC Outgoing Circuits Monitoring ● A+B Dual-side independent AC Circuits Monitoring ● Full Electrical Parameters Monitoring ● Outgoing Branch Circuits Multi-metering |
Multiple Branch Circuits Metering ● Both 1-phase&3-phase Metering ● Max 36 circuits 1-phase ● Max 12 circuits 3-phase ● Mixed 8 circuits 3-phase and 12 circuits 1-phase for example |
Power Quality Analysis ● 2nd~31st Harmonic ● Total Harmonic |
Switch On/Off Status Detection ● A+B Dual Side ● 48-channel of DI (Digital Input) |
Application in Data Center
Wiring Illustration
PIN/Terminal Overview of AMC16Z-FAK48
Wiring Diagram
Voltage&Current Input Wiring of AMC16Z-FAK48 (Demo for A side partial wiring)
Dimension
Technical parameters | AMC16Z-FAK24 | AMC16Z-FAK48 | ||||||
Measurement parameters | Voltage, current, frequency, active power, reactive power, power factor, activepower, reactive power, switching state | |||||||
2-31 times harmonics | ||||||||
Bus Voltage | Rated | 220VAC | ||||||
Measurement | ±20% | |||||||
Overload | Instantaneous voltage 2 times/second | |||||||
Currentoutgoing line loop | Rated | 50mA | ||||||
Range | 0.125~60mA | |||||||
Overload | Duration 1.2 times, instantaneous 10 times/second | |||||||
Input frequency | 45~60Hz | |||||||
Measurement accuracy | Outgoing line | Voltage/current/active power/active energy level 0.5, reactive power/reactive energy level 1 | ||||||
Auxiliary power supply | Power supply by AMC16Z-ZA | |||||||
Environment | Temperature | Working:-15℃~55℃ Storage:-25℃~70℃ | ||||||
Humidity | Relative humidity | |||||||
Altitude | ≤2500m | |||||||
Communication | RS485/Modbus-RTU | |||||||
Installation method | DIN35mm Guide rail or bottom plate mounting | |||||||
IP grade | IP20 | |||||||
Class of pollution | 2 | |||||||
Safety | Insulation | All terminals and the insulation resistance between the conductive pieces not below 100 m Ω | ||||||
Withstand voltage | A-channel voltage and current signal // B-channel voltage and current signal // other ports meet AC2kV 1min between pairs, leakage current should be less than 2mA, no breakdown or flashover phenomenon. | |||||||
Electromagneticcompatibility | Anti static interference | Level 4 | ||||||
Resistance toradiation ofRadio frequencyelectromagneti | Level 3 |