● Measurement: 3-phase AC kWh, kVarh, U, I, P, Q, S, PF, F and etc
● Accuracy: 0.5% (kWh)
● Frequency: 45~65Hz
● Rated Voltage: 3×380~456Vac L-L (direct connect); 3×100~120Vac L-L (via PTs)
● Rated Current: 3×10(80)A AC (direct connect); 3×1(6)A AC (via CTs)
● Communication: RS485 (MODBUS-RTU)
● Multi-rate: 4 Tariff Rates and etc
● Data Function: Frozen Data,Max Demand,etc
● Harmonic: 2~31st and total Harmonic
● Standard&Certificate: IEC; CE;CE-MID; EAC
Overview
ADL400 is a smart meter designed for power supply system, industrial and mining enterprises and utilities to calculate the electricity consumption and manage the electric demand. It features the high precision, small size and simple installation. It integrates the measurement of all electrical parameters with the comprehensive electricity metering and management provides various data on previous 48 months, checks the 31st harmonic content and the total harmonic content. It is fitted with RS485 communication port and adapted to MODBUS-RTU .ADL400 can be used in all kinds of control systems, SCADA systems and energy management systems. The meter meet the related technical requirements of electricity meter in the IEC62053-21standards.Main Functions
Panel Overview
Main Parameters
Main Features
Diverse Electric Parameters Measurement ● kWh (3-phase positive Kilowatt-hours) ● kVarh (Kilovar-hours) ● Harmonic (2~31st voltage¤t)—Standard ● U (3-phase Voltage) ● I (3-phase Current) ● P (Power) ● Q (Reactive power) ● F (Frequency) ● S (Apparent power) ● PF (Power factor) |
Multi-rate/Flexible Tariff ● 4 Time zone ● 4 Tariff rate (Spike, Peak, Flat, Valley) ● 2 Time period list ● 14 Time period by day ● Data Frozen (last 48 months or last 90 days) ● Max demand and occurrence time |
HMI for Common Configuration ● PT or CT ratio ● Wiring methods (3P4W or 3P3W) ● Back linght time ● RS485 (MODBUS-RTU) communication setting |
Outline Dimension
Dimension of ADL400 (Current Input via Direct Connect)
Dimension of ADL400 (Current Input via CTs)
Direct Connect Type
PIN/Terminal Overview of ADL400 (Direct Connect Type)
Power Wiring: 3-phase 4-wire via direct connect
Power Wiring: 3-phase 3-wire via direct connect
RS485 Wired Communication of ADL400 (Direct Connect Type) with IoT Gateway
CT Operated Type
PIN/Terminal Overview of ADL400 (CT Operated Type)
Power Wiring: 3-phase 4-wire CT operated
Power Wiring: 3-phase 3-wire CT operated
RS485 Wired Communication of ADL400 (CT Operated Type) with IoT Gateway
DIN Rail Installation
Application in IoT System
project | performance parameter | ||
Specification | 3 phase 3 wires, 3 phase 4 wires | ||
Measurement | Voltage | Reference voltage | 3×100V、 3×380V、3×57.7/100V、 3×220/380V |
Consumption | <10VA(Single phase) | ||
Impedance | >2MΩ | ||
Accuracy class | Error±0.2% | ||
Current | Input current | 3×1(6)A, 3×10(80)A | |
Consumption | <1VA Single phase rated current | ||
Accuracy class | Error±0.2% | ||
Power | Active, reactive, apparent power, error±0.5℅ | ||
Frequency | 45~65Hz,Error±0.2% | ||
Metering | Energy | Active energy(Accuracy class: 0.5)reactive energy(Accuracy class 2) | |
Clock | ≤0.5s/d | ||
Digit signal | Energy pulse output | 1 active photocoupler output | |
pulse | Width of pulse | 80±20ms | |
Pulse constant | 400imp/kWh,10000imp/kWh(Correspond with the basic current) | ||
communication | Interface and communication protocol | RS485口:Modbus RTURS485:Modbus RTU | |
Range of communication address | Modbus RTU:1~ 247; | ||
Baud rate | 1200bps~19200bps | ||
environment | working temperature | -25℃~+55℃ | |
Relative humidity | ≤95℅(No condensation) |