● Insulation fault location in AC IT systems
● AIL150-4: 4 measuring channels
● AIL150-8: 8 measuring channels
● LED indicators: On, Comm
● CAN bus
● Auxiliary power supply: DC24V
Overview
AIL150-4 4 channels Insulation Fault Locator in conjunction with AIM-M200 medical intelligent insulation monitor and ASG150 test signal generator,are designed for insulation fault location in medical IT systems.The locating current generated by ASG150 are detected using the integrated measuring current transformers and evaluated by the insulation fault locators.Dimension
Wiring
Typical Connection
Model Selection
Application programme-ICU/CCU
Typical Connection
Item | Technical parameters | |
AIL150-4/AIL150-8/AIL160-6 | ||
Auxiliary power supply | Voltage | DC 18…36V |
Maximum power consumption | ≤2VA | |
Monitored system | Rated voltage | 0…242 VAC |
Rated frequency | 45… 60Hz | |
Fault locating | Maximum circuit | 4,8,6 Loops |
Response time | ≤5s | |
Communication | Mode | CAN communication |
Protocol | Self-defined protocol |