● Measurement: 3-phase kWh, kVarh, kW, I, U, Hz, Cosφ, Current&Voltage Unbalance, 2~63rd Harmonic, Real-time&Max Demand, Zero-sequence Current, 4-quadrant Energy and etc
● Current Rating: -/5A AC; -/1A AC (According to CTs)
● Voltage Rating: 100V, 110V, 400V, 690V AC
● Frequency: 45~65Hz
● Accuracy: Up to 0.2S (Optional)
● Communication (Main Body): RS485 (MODBUS-RTU)
● Communication (Expanded): PROFIBUS-DP; Ethernet; Secondary RS485
● Extra Function: 8DI/2DO; 8AI/4AO; SOE (with standard 4GB SD Card); Multi-rate
● Display: LCD Display
● Dimension: 96*96*90mm (L*W*H)
● Installation: Panel Embedded (Cut-out –92*92mm)
● Power Supply: 85~265V AC/DC; 115~415V AC/DC
● Standard&Certificate: CE
Overview
APM series power meters of ACREL are power meters that are designed according to IEC standards and synchronized with international advanced technology. APM series meters have full power measurement, energy statistics, analysis of power quality and network communications and other functions, are mainly used for comprehensive monitoring of the quality of power supply network. This series of meters use a modular design, with a rich function of the external DI / DO module, AI / AO module, event recording (SOE) module with T-Flash (TF) card, network communication module, Temperature and humidity measurement module, can achieve full power measurement of electrical circuit and monitoring of switch status, Dual RS485 with Ethernet interface can realize data copying of RS485 master station, eliminating the need for data switching exchange. PROFIBUS-DP interface can realize high-speed data transmission and networking function.Features
Full Electric Parameters Measurement ● 3-phase (I, U, kW, kVar, kWh, Hz, cosφ) ● Current&Voltage Unbalance ● Harmonic (THD & 2~63rd) ● Real-time&Max Demand ● Extremum of this month&last month ● Zero-sequence Current ● 4-quadrant Energy |
Diverse Extra Function Module ● Modular Design (Easy for Function Expansion) ● Support up to 3 Expanded Module at same time |
DO/DI Switch Function Module —MD82 ● 2 DO Relay Output ● 8 DI Digital Input ● Save up to 128 pcs DO/DI Data in Main Body ● Paired with MLOG to save more DO/DI Records |
SD Card Data Storage Module —MLOG ● Expand Number of SOE Storage ● Support Storage of SD Cards up to 32GB (standard 4GB) |
Extra RS485 Communication Module —MCM ● Interface: RS485 Interface ● Protocol: MODBUS-RTU ● Support Salve&Master Mode |
Ethernet Communication Module —MCME ● Interface: RJ45 Interface ● Protocol: MODBUS-TCP/HTTP/DHCP/SMTP ● Could Serve as Serial Server ● Plus 1 Extra RS485 Interface |
PROFIBUS-DP Communication Module —MCMP ● Interface: PROFIBUS-DP Interface ● Protocol: PROFIBUS-DP ● Plus 1 Extra RS485 Interface |
SOE Function (Main Body) ● Alarm Record (128 pcs records of 66 kinds&13 categories) ● DO/DI Record (128 pcs DO/DI records) ● Transient Record (800 pcs transient waveform records) ● Max Records pcs above could be expanded by SD Card |
Multi-rate/Multi-tariff ● 4 Time zone ● 4 Tariff rate (Spike, Peak, Flat, Valley) ● 2 Time period list ● 14 Time period by day |
Local Configuration ● Keypads HMI for Programming ● Setting through Adjustment Software ● Setting through WEB ● Setting through MODBUS communication |
Wiring Illustration
3-phase 4-wire connection via 3 extra CTs
3-phase 3-wire connection via 2 extra CTs & 2 extra PTs
Technical Parameters | Index | |||
Signal | Electrical network | Three-phase three-wire, three-phase four-wire, see the wiring diagram; | ||
Frequency | 45~65Hz; | |||
Voltage | Rated value:AC 100V、110V、400V、690V; | |||
Overload: 1.2 times rated value(continuous); 2 times rated value /1 second; | ||||
Power consumption: < 0.5VA (per channel); | ||||
Current | Rated value: AC 1A, 5A, support 4 mm2 line access; | |||
Overload: 1.2 times rated value(continuous); 10 times rated value/1 second; | ||||
Power consumption: < 0.5VA (per channel); | ||||
Measurement accuracy | Voltage、current and power | class 0.5s/class 0.2s (APM800、APM810/APM801/APM830) | ||
Active power | class 0.5s/class 0.2s (APM800、APM810/APM801/APM830) | |||
Reactive power | class 2 | |||
Harmonic | 1%(2rd~42nd)、2%(43rd~63rd) | |||
Switch inputs | Dry contact inputs, built-in power supply; | |||
Relay outputs | Contact type: open contact in main part, changeover contact in module;Contact capacity:AC 250V/3A DC 30V/3A; | |||
Pulse output of energy | Output mode: Optocoupler pulse with open collector;Pulse constant:4000(5A)、8000(1A) imp/kWh; | |||
Analog outputs | DC 0mA~20mA、4mA~20mA、0V~5V、1V~5V output, accuracy class 0.5%, load resistance ≤ 500Ω; | |||
Analog inputs | DC 0mA~20mA、4mA~20mA、0V~5V、1V~5V iutput, accuracy class 0.5% | |||
Storage card | Standard Capacity:4G,TF Card Up to 32G Capacity; | |||
Communication | RS485 interface/Modbus-RTU protocol and DLT645 protocolProfibus-DP interface/Profibus-DP protocol;RJ45 interface (Ethernet) / Modbus-TCP, http, DHCP and other protocols; | |||
Power supply | Working range: AC/DC 85V~265V or AC/DC 115~415V(P2);Power consumption: Power consumption of the main part ≤ 15VA; | |||
Safety | Power frequency withstand voltage | The power frequency withstand voltage between the shell and the auxiliary power supply, each input and output terminal group is AC 4kV/1min;The power frequency withstand voltage between the auxiliary power supply and each input and each output terminal group is AC 2kV/1min;The power frequency withstand voltage between the voltage input and other input/output terminal groups is AC 2kV/1min;The power frequency withstand voltage between the current input and other input/output terminal groups is AC 2kV/1min;The power frequency withstand voltage between the relay output and other input/output terminal groups is AC 2kV/1min;The power frequency withstand voltage between each terminal group of switch input, communication, analog output and pulse output is AC 1kV/1min; | ||
Insulation resistance | Inputs、outputs to the shell>100MΩ; | |||
Electromagnetic compatibility | Meet IEC 61000 standard (Level 4); | |||
Protection level | Display panel IP52 | |||
Environment | Operating temperature: -20 °C ~ +65 °C;Storage temperature: -20°C~+70°C;Relative humidity: ≤95% without condensation;Altitude: ≤2500m; | |||
Standards | IEC 60068-2-1IEC 60068-2-2IEC 60068-2-30 | Environmental Testing-Part 2-1:Tests Test A:Cold IDAPart 2-1:Tests Test B:Dry heatPart 2-30:Tests Test Db:Damp heat,cyclic(12+12h) | ||
IEC 61000-4 | Electromagnetic compatibility-Testing and measurement techniques | |||
IEC 61557-12 | Electrical safety in low voltage distribution system up to 1000V a.c. and1500V d.c –Equipment for testing,measuring or monitoring of protective measures- Part12:Performances measuring and monitoring devices(PMD) | |||
IEC 62053-22 | Electricity metering equipment (a.c.)-Particular requirements – Part22:Static meter for active energy(class 0.2s and 0.5s) |