● Insulation monitoring for medical IT systems
● Load and temperature monitoring of isolation transformer
● Device disconnection monitoring
● LED indicators: On, Insulation, Overload, Overtemp
● Alarm relay output
● Test button
● Insulation fault location
● Din 35mm
● RS485 (MODBUS-RTU) + CAN
Overview
The AIM-M100 medical isolated meter the insulation resistance of medical IT system, At the same time, the load current and temperature of the IT system transformer is monitored. In combination with ASG100, AIL100 series insulation fault locators and the appropriate measuring current transformers, the AIM-M100 is designed to support insulation fault location.Dimension
Wiring
Model Selection
Application programme-ICU/CCU
Typical Connection
Auxiliary power supply | Voltage | AC220V (±10%) | Temperature measurement | Thermistor | Pt100 |
Frequency | 50/60Hz | Measuring range | -50~+200℃ | ||
power consumption | <8W | Alarm value scope | 0~+200℃ | ||
Insulation monitoring | Range of insulation resistance | 10~999kΩ | Alarm output | Output mode | 2-route relay output (optional) |
Absolute percentage | 0~±10% | Contact capacity | AC 250V/3A;DC 30V/3A | ||
Alarm value scope | 50~999kΩ | Environment | Operating temperature | -10~+55℃ | |
Response time | <2s | Storage temperature | -20~+70℃ | ||
Measuring voltage | <12V | Relative humidity | 5%~95%, non-condensate | ||
Measuring current | <50uA | Altitude | ≤2500m | ||
Load current | Measuring range | 2.1~50A | Communication | RS485, Modbus-RTU | |
Alarm value scope | 5~50A | Rated impulse voltage/ Pollution degree | 4KV/Ⅲ | ||
Measuring accuracy | ≤±5% | EMC electromagnetic compatibility/ Electromagnetic radiation | Conform to IEC 61326-2-4 |