● Measurement: 1-phase AC kWh, Active Power, Current, Voltage and etc
● Accuracy: 1.0% (kWh)
● Frequency: 45~65Hz
● Rated Voltage: 220~264Vac (direct connect)
● Rated Current: 10(80)A AC (direct connect)
● Communication: RS485 (MODBUS-RTU)
● Multi-rate/tariff: 4 Tariff Rates and etc
● Dimension: 90*36*65mm (L*W*H)
● Installation: 35mm DIN Rail
● Standard&Certificate: IEC; CE;CE-MID;EAC
Diverse Electricity Parameters Measurement ● U (Voltage) ● I (Current) ● P (Power) ● Q (Reactive power) ● S (Apparent power) ● PF (Power factor) ● kWh (Kilowatt-hours)● kVarh (Kilovar-hours) |
Multi-rate/Flexible Tariff ● 4 Time zone ● 4 Tariff rate (Spike, Peak, Flat, Valley) ● 2 Time period list ● 14 Time period by day |
HMI for Parameters Setting ● Code ● Protocol ● Address ● Baud rate ● Parity ● All Display |
PIN/Terminal Overview of ADL200
Wiring DiagramPower Wiring: 1-phase 2-wire via direct connect
Communication Wiring: RS485 wired Communication with IoT Gateway
DIN Rail Installation Application in IoT SystemFunction | Function description | Function provide |
Measurement of kWh | Single-phase active kWh (positive and negative),3 months historical energy data frozen storage | ■ |
Measurement of electrical parameters | Voltage, Current, Active power, Reactive power, Apparent power, Power factor and Frequency | ■ |
LCD Display | 8 bits section LCD display | ■ |
Key programming | 3 keys to set parameters like code, address, baud rate, multi-tariff and communication protocol | ■ |
Pulse output | Active energy pulse output | ■ |
Multi-tariff | Adapt 4 time zones, 2 time interval lists, 14 time interval by day and 4 tariff rates | □F |
Communication | Communication interface: RS485, Communication protocol: MODBUS-RTU | ■C |
Input voltage | Reference voltage | AC 220V |
Reference frequency | 50Hz | |
Power consumption | <10VA | |
Input current | Basic current | 10A |
Maximum current | 80A | |
Starting current | 4‰Ib | |
Consumption | <4VA | |
Measurement performance | Accuracy of measuring | 1 class |
Range of measuring | 000000.00~99999999kWh | |
Clock accuracy | Error≤0.5s/d | |
Active pulse | Pulse width | 80±20ms |
Pulse constant | 1000imp/kWh | |
Communication | Interface | RS485(A+、B-) |
Connection mode | Shielded twisted pair conductors | |
Protocol | MODBUS-RTU |