● Measurement: 3-phase AC kWh, kVarh, I, U, kW, kVar, Hz, cosφ and etc
● Accuracy: 1% (kWh); 0.5% (Active Power)
● Rated Voltage: 400V AC L-L (direct connect); 100V AC L-L (via PTs)
● Rated Current: 5A AC or 1A AC (via CTs)
● Power Supply: 85~265V AC/DC; 24V or 48V DC
● Communication: RS485 (MODBUS-RTU)
● SOE Funciton: Event&Demand&Extremum Record
● Harmonic Measurement: 2~31st and total Harmonic
● Analog Output: 4~20mA DC or 1~5V DC
● DI/DO Function: 2/4-channel DI&2-channel DO
● Standard&Certificate: CE Certificates
AC Voltage Signal (400V AC L-L) Input via direct Connection & AC Current Signal (5A or 1A AC) input via -/5A AC or -/1A AC CTs (3-phase 4-wire)
AC Voltage Signal (400V AC L-L) Input via direct Connection & AC Current Signal (5A or 1A AC) input via -/5A AC or -/1A AC CTs (3-phase 3-wire)
AC Voltage Signal (100V AC L-L) Input via -/100V AC PTs & AC Current Signal (5A or 1A AC) input via -/5A AC or -/1A AC CTs (3-phase 4-wire)
AC Voltage Signal (100V AC L-L) Input via -/100V AC PTs & AC Current Signal (5A or 1A AC) input via -/5A AC or -/1A AC CTs (3-phase 3-wire)
Installation Instruction1. Cut out a hole on the object on where we will intall the meter according to dimension of meter referred above. 2. Remove the buckle on the meter off. |
3. Install the meter into the cut-out hole. 4. Buckle up and fixed the meter. |
Technical parameters | Value | |||
Input | Connection | Single phase-2-wire, 3-phase-3-wire, 3-phase-4-wire | ||
Frequency | 45-65Hz | |||
Voltage | Rating:single-phase :AC 100V、400VThree-phase: AC 3×57.7V/100V(100V)、3×220V/380V(400V)、3×380V/660V(660V)(96 size only) | |||
Overload:1.2 fold rating {continuous) : 2 fold rating for 1 second | ||||
Power consumption:< 0.5VA | ||||
Current | Rating: AC IA、5A | |||
Overload:1.2 fold rating(continuous);10fold rating for 1 second | ||||
Power consumption:< 0.5VA | ||||
Output | Electric energy | Output mode:open-collector photo-coupler pulse | ||
Pulse constant: 10000imp/kWh(settable),see wiring diagram for details; | ||||
Communication | RS485port, Modbus -RTU protocol,DLT645 protocol(versions 07 and 97),baud rate 1200 ~ 38400 | |||
Function | Switching input | Dry contact input, built-in power supply;if the model is KA,it is AC 220V active. | ||
Switching output | Output mode: Relay normally open contact output | |||
Contact capacity: AC 250V/3A、 DC 30V/3A | ||||
Analog output | 1-5V,4 – 20mA | |||
Accuracy class | Frequency:0.05Hz,Current、Voltage:0.2 class,Reactive power:l .0class,Reactive Electric energy:l .0class, active power:0.5class,active electric energy: 0.5class,2-31th harmonic measurement:±1% | |||
Power supply | AC/DC 85-265V or DC24V(±20%)or DC48V(±20%)power consumption≤10VA | |||
Security | Power frequency withstand voltage | Between Power supply//Switching Output// Current Input//voltage Input and Transmitting// Communication //Pulse Output//switching input AC 2 kV 1min;Between Power supply、switching output、Current Input、voltage Input AC 2 kV 1min;Between Transmitting、Communication、Pulse Output、switching input AC 1kV 1 min; | ||
Insulation resistance | Input、Output end to machine enclosure >100MΩ | |||
Environment | Temperature | work: -25°C~+65°C storage: -40°C ~+80°C | ||
Humidity | ≤93%RH Non-condensing | |||
Altitude | ≤2500m |